Defender DSP 3.3 40 kVA UPS

Defender DSP 3.3 40 kVA UPS

Download Catalogue (PDF) Request a Quote

The Defender DSP 3340 is a 40 kVA online double conversion UPS unit with a DSP controlled IGBT rectifier. It takes a 380/400/415 VAC three phase input and delivers a three phase output at 0.8 output power factor (32 kW), with zero transfer time and a maintenance bypass.

Features

  • Real online double conversion structure
  • Wide input voltage range
  • Zero transfer time
  • Protection against mains power problems
  • Low input voltage harmonics
  • Low installation cost
  • High reliability and performance
  • Maintenance bypass
  • RS232 and smart slot interface
  • 3 phase input and 3 phase output
  • Event log
  • Can operate as a 50/60 Hz or 60/50 Hz frequency converter
  • Voltage adjustment via LCD panel (208/220/230/240 VAC)
  • Turkish and English menu
80-300 VWide Voltage Range
95%High Efficiency
50/60 HzOutput Frequency

Defender DSP Series Technical Specifications

Online “Double Conversion” Technology, DSP Controlled IGBT Rectifier UPS

  • IGBT Rectifier
  • Real Digital Signal Processor (DSP) controlled transformerless design
  • Input Power Factor Correction PFC( >0,99 )
  • Low Total Harmonic Distortion Level
  • High Efficiency ( up to 95% )
  • Wide Input Voltage Range
  • Generator Compatible Operation
  • ECO Mode Feature
  • Intelligent battery management system extends the lifetime of batteries
  • Static and Manual Bypass
  • Communication with computers and network systems with SNMP availability
  • Expandable battery blocks
  • Low installation and operating costs
  • Special voltage applications other than stated values
ModelDefender DSP 3340
MODEL
Output Power (kVA)40
Nominal Active Power (kW)32
INPUT
Number Of Phases3Phase+N+E
Nominal Voltage (Ph-Ph)380/400/415VAC
Voltage Range (100% Load)176-280 VAC
Nominal Frequency (Hz)50/60 Hz
Frequency Range44-66 HZ
Input Current THD<4%
Input Power Factor0.99
OUTPUT
Power Factor0,8
Number Of Phases3
Voltage380/400/415
Static Voltage Regulation1%
THD-V<3%
Crest Factor3:1
Frequency (Hz)50 / 60 Hz
Free Running Frequency (Hz)0.01 Hz
Overload125% for 10 minutes, 150% for 30 secs
Efficiency>94%
BATTERY
TypeMaintenance Free Dry Type
Quantity2×31
Battery ProtectionDeep Discharge Protection with Auto Cut Off
Battery TestStandard ( Auto&Manual)
DISPLAY
LED DisplayLine, Bypass, Battery, Inverter, Load, Fault Indications
LCD DisplayLoad%, Input&Output Frequency, Voltage & Current, Bypass Voltage, Battery Voltage & Current, Temperature, Alarms, History
STATIC BYPASS
Number Of Phases3Phase+N+E
Voltage Range For Bypass175-253 VAC
Frequency Range For Bypass47-53 Hz or 57-63 Hz
COMMUNICATION
Interface (Communication Ports)RS 232
Dry Contact SignalsOptional
OthersSNMP Optional
ENVIRONMENT
Storage Temperature Range (°C)Without Batteries -25 +55 C (15 to 40 recommended for longer battery life time)
Operating Temperature Range (°C)0-40 C (20 to 25 recommended for longer battery life time)
Relative Humidity0-95 % (non-condensing)
Max. Altitude1000 m
Protection LevelIP 20
PHYSICAL SPECIFICATIONS
Dimensions W*D*H (cm)46x94x116
Weight (kg)120
STANDARDS
StandardsCE

Specifications from the official UPSet product catalogue. Specifications are subject to change without prior notice.

Get Offer!