PA 6-10 kVA UPS

UPSet PA Series 6-10 kVA Single Phase Online UPS

Download Catalogue (PDF) Request a Quote

The PA-6000 and PA-10000 are 6 and 10 kVA single phase online UPS units with power factor 1.0 (kVA = kW) and pure sine wave output. They use a 192 VDC battery bank (16 x 12V 7/9Ah) and offer selectable output voltage, cold start and 0 ms transfer from AC mode to battery mode.

PA Series 6-10 kVA – Single Phase Online UPS

VFIOnline UPS
1.0Power Factor (kVA = kW)
0 msTransfer Time
LCDDisplay, USB, Plug & Play

Features

  • Microprocessor control
  • High reliability
  • Selectable output voltage
  • Power factor 1.0 (kVA = kW)
  • Automatic voltage regulation (AVR)
  • Emergency power off (EPO)
  • Pure sine wave output
  • Cold start (built-in DC start) and auto restart on AC recovery
  • Replaceable battery design
  • 50/60 Hz frequency auto-sensing
  • Lightning, overcurrent and deep discharge protection
  • Battery low and overload alarm
  • Energy consumption calculation (optional)
  • Color options: black / white

Backup time with internal batteries at 50% load is shown in the datasheet. Backup time is extendable based on custom requirements.

Technical Specifications

ModelPA-6000PA-10000
MODEL
Capacity6kVA / 6kW10kVA / 10kW
INPUT
Input SystemL+N+PE
Rated Voltage208/220/230/240 VAC
Voltage Range110 VAC ~ 300 VAC
100 VAC ~ 176 VAC
280 ~ 300 VAC (Power Limited)
Frequency50/60 ±6 Hz (Default), ±10 Hz (Can be Set)
Power Factor0.99
OUTPUT
Output SystemL+N+PE
Power Factor1.0
Voltage208/220/230/240 VAC
Wave FormPure Sine Wave
Harmonic Distortion (THDv)≤3% (0~100% Linear Load)
≤5% (0~100% Non Linear Load)
Frequency50 Hz / 60 Hz ±0.05% Hz (Battery Model)
Inverter Overload Capacity (Normal Mode 25 °C)AC Mode: 30min @ 102-110% / 10min @ 110-130% / 30sec @ 130-150% / 200ms @ >150% load
Battery Mode: 1min @ 102-110% / 10sec @ 110-130% / 3sec @ 130-150% / 200ms @ >150% load
Transfer TimeAC Mode to Battery Mode: 0ms
Inverter to Bypass Mode: 4ms
BATTERY
Battery Capacity7/9Ah7/9Ah
Battery Voltage192Vdc
Charge Current1A (Default), 1-12A Settable (Optional)
Capacity / Volts / Quantity16 x 12V x 7/9Ah (16 pcs)
Charging Duration90% of Battery Capacity in 8 hrs (Standard Type)
INTERFACE
RS-232Windows 2000/2003/XP/Vista/2008/7, Linux, Unix and MAC
USBWindows Family & MAC
Intelligent Slot (Optional)SNMP
ENVIRONMENTAL
Operating Temperature0~40°C
Relative Humidity20%~95% (No Condensation)
AltitudeShould not exceed 1000m, derating above 1000m, up to 4000m (max), refer IEC62040
Noise≤50 dB
Storage Temperature15~60°C (Battery: 0~40°C)
DIMENSIONS & WEIGHT
Dimensions (WxDxH) (mm)192x470x612
Net Weight (kg)5258
Color (Options)Black / White