Valita L 220V 10-120 kVA Low Frequency 3 Phase Online UPS

Valita L 220V 10-120 kVA Low Frequency 3 Phase Online UPS

Download Catalogue (PDF) Request a Quote

The Valita L 220V series is a 10-120 kVA tower UPS with 3P/3P online double conversion, backfeed protection and true sine wave output, built on transformer-based (low frequency) technology with an isolation transformer. It is designed for 220V three-phase input and 220V three-phase output, for applications such as government, finance, IT, education, transportation, broadcasting, medical and energy.

Features

  • Tower UPS with isolation transformer, transformer-based technology
  • 220V three-phase input and 220V three-phase output
  • Touch LCD with IoT functions
  • IGBT rectifier and inverter
  • Generator compatible
  • Front access makes maintenance and replacement easy
  • Online double conversion with backfeed protection, true sine wave output
10-120 kVAPower Range
1Output Power Factor
>0.99Input Power Factor

Valita L 220V Series Technical Specifications

10-40 kVA

ModelValita 22010Valita 22015Valita 22020Valita 22030Valita 22040
Rated Power10kVA15kVA20kVA30kVA40kVA
MAIN INPUT
Input3P5W (3P+N+PE)
Rated Voltage200/208/220VAC (L-L)
Rated Frequency50/60Hz
Input PF>0.99
Current DistortionTHDi <2% (100% linear load)
Voltage Range146-270VAC (166-250VAC full load)
Frequency Range50/60Hz ±5%
BATTERY
Rated Voltage360VDC (default 30 pcs, 28-32 pcs selectable)
Charging Current1.8A (default), settable according to the battery settings
INVERTER
Rated Voltage200/208/220VAC (L-L)
Rated Frequency50/60Hz
Output PF1
Voltage Accuracy±1.0%
Output THDu<1% (linear load), <5% (non-linear load)
Overload105% long time running
105-110% transfer to bypass in 1h
110-125% transfer to bypass in 10 mins
125-150% transfer to bypass in 1 min
150-200% transfer to bypass in 100 ms
>200% transfer to bypass in 100 ms
Frequency Accuracy0.1%
Crest Factor3:1
SYSTEM
Efficiencyup to 90% (95% in ECO mode)
DisplayLED + 7 inch touch LCD
Safety CertificationIEC62040-1, IEC60950-1
EMS CertificationIEC62040-2; IEC61000-4-2 (ESD); IEC61000-4-3 (RS); IEC61000-4-4 (EFT); IEC61000-4-5 (Surge)
IP DegreeIP20
ConfigurationRS232, RS485, dry contact
OptionsSNMP card, AS400 card, parallel kit
Environment0-40°C (operation); -25°C ~ 70°C (storage); 0-95% (humidity, non-condensing)
PHYSICAL
Dimension W×D×H (mm)500*800*1600
Weight (kg)297297325372402

50-120 kVA

ModelValita 22050Valita 22060Valita 22080Valita 220100Valita 220120
Rated Power50kVA60kVA80kVA100kVA120kVA
MAIN INPUT
Input3P5W (3P+N+PE)
Rated Voltage200/208/220VAC (L-L)
Rated Frequency50/60Hz
Input PF>0.99
Current DistortionTHDi <2% (100% linear load)
Voltage Range146-270VAC (166-250VAC full load)
Frequency Range50/60Hz ±5%
BATTERY
Rated Voltage360VDC (default 30 pcs, 28-32 pcs selectable)
Charging Current100A150A150A200A200A
INVERTER
Rated Voltage200/208/220VAC (L-L)
Rated Frequency50/60Hz
Output PF1
Voltage Accuracy±1.0%
Output THDu<2% (linear load), <8% (non-linear load)
Overload105% long time running
105-110% transfer to bypass in 1h
110-125% transfer to bypass in 10 mins
125-150% transfer to bypass in 1 min
150-200% transfer to bypass in 100 ms
>200% transfer to bypass in 100 ms
Frequency Accuracy0.1%
Crest Factor3:1
SYSTEM
Efficiencyup to 90% (95% in ECO mode)
DisplayLED + 7 inch touch LCD
Safety CertificationIEC62040-1, IEC60950-1
EMS CertificationIEC62040-2; IEC61000-4-2 (ESD); IEC61000-4-3 (RS); IEC61000-4-4 (EFT); IEC61000-4-5 (Surge)
IP DegreeIP20
ConfigurationRS232, RS485, dry contact
OptionsSNMP card, AS400 card, parallel kit
Environment0-40°C (operation); -25°C ~ 70°C (storage); 0-95% (humidity, non-condensing)
PHYSICAL
Dimension W×D×H (mm)600*800*1600800*900*1800
Weight (kg)460590630690

Specifications from the official Valita catalogue (Valita-L-220V-Low-Frequency-10-120kVA-2026.pdf). Specifications are subject to change without prior notice.